亚洲综合网曝日韩,欧美精品福利在线视,亚洲AV永久无码精品网站,久热免费视频,亚洲欧美国产高清vA在线播放,亚洲人妻系列

首頁
視頻
讓中國物聯(lián)網(wǎng)領(lǐng)先世界
搜索
歷史搜索
搜索發(fā)現(xiàn)
HOME > SERVICE > Problem > I/O

Linear transformation formula

2022-03-31 10:45:43| | 0

0-10V corresponds to 0-10000. If you need to set the trigger according to the actual sensor data, you need to calculate the trigger threshold. The conversion formula is y=ax+b, y is the actual sensor value, x is the original value of the current, a is the proportional coefficient, and b is the Linear coefficient, for example: 4-20ma temperature sensor, the range is -40-120°C, the conversion formula is: y=0.01x-80, when 20°C is the trigger threshold, the current original value is 20=0.01x- 80, the original value of the current is 10000.


4-20ma corresponds to 4000-20000. For example, the upper and lower limits of the connected temperature sensor are 0-100°C. but:


Write a linear relationship according to the conversion formula (y=ax+b)


0=4000a+b


100=20000a+b


Solution a=0.00625 b=-25


That is, the linear relationship is y=0.00625x-25


聯(lián)系銷售
銷售王經(jīng)理微信 銷售王經(jīng)理
微信公眾號 微信公眾號
服務(wù)熱線
400-6688-400
安吉县| 五大连池市| 合阳县| 闵行区| 乌鲁木齐市| 自治县| 贺州市| 壤塘县| 怀宁县| 南京市| 临洮县| 莱州市| 山阳县| 正蓝旗| 四会市| 通渭县| 柳州市| 手机|